Gasfitter Class B Red Seal Practice Quiz
Free · 158 Questions.

Based on the Red Seal Gasfitter Class B exam blueprint: gas piping and tubing, venting and air supply, controls and electrical, appliances and conversions, testing and commissioning, service and repair

📝 100 Q practice test✅ Pass: 70%⏱ Up to 4 hr🔁 Free retakes Updated: October 2026
⚠️ExamHub is an independent study resource and is not affiliated with, endorsed by, or reviewed by the Red Seal program, CSA Group or any provincial regulator. Questions are original practice materials.
Choose your mode
Mode 1
Test Me
100 questions with a 240-minute timer. 70% (70/100) to pass, with complete answer review at the end.
⏱ 240 min100 Qs70% to passAnswer review
Mode 2
Practice
Sequential practice with detailed explanations after every question. Numbered navigator with auto-saving progress.
📖 Explanations🔊 Voice narrationAuto-save
Or practice by topic
Common Occupational Skills
11 questions
Fuel Piping and Tubing
23 questions
Venting, Air Supply and Draft Control
28 questions
Controls and Electrical Systems
24 questions
Appliances, Conversions and Fuel Storage
25 questions
Testing and Commissioning
24 questions
Maintenance, Repair and Decommissioning
23 questions
📲 Add Gasfitter Class B Red Seal Practice Quiz to your Home Screen

Practice on the go and jump straight back to where you left off.

About the certification

Gasfitter – Class B (Red Seal) certification

The official Red Seal trade name is Gasfitter – Class B. A Class B gasfitter installs, converts, tests and services gas piping and gas-fired appliances up to 400,000 Btuh, such as furnaces, boilers, water heaters and residential or light-commercial equipment. Class A has no input limit. Passing the interprovincial Red Seal exam, with the provincial requirements, earns the Red Seal endorsement.

Exam details as of October 2026, from the Red Seal Gasfitter – Class B exam information page and the Red Seal Exam Preparation Guide.

Exam detail
Exam detailValue
Questions100, multiple choice (four options)
Blocks7 (A to G)
Pass mark70%
Writing time4 hours
Code bookSupplied at the exam; SkilledTradesBC lists the B149.1 Natural Gas and Propane Installation Code as the code book provided
Question typesProcedural and application 50-60%, recall 25-35%, critical thinking 10-20%

ExamHub's free Gasfitter Class B practice quiz has 158 original questions weighted to the exam blocks, with an explanation and a source for every answer. The CSA B149.1 code is a paid standard, so each question cites the public document that quotes the clause: the Red Seal standard, regulator bulletins from Alberta, British Columbia and Ontario, open trade textbooks and manufacturer instructions. Questions that rest on one province's rules say so. See how ExamHub checks its questions.

Studying for the Ontario licence instead? Try the TSSA G3 Gas Technician practice test. Gas work also overlaps with the 306A Plumber and 307A Steamfitter trades.

What's covered

158 practice questions, by category

Categories follow the 7 Red Seal exam blocks, weighted like the real exam.

Block / topicExam QBank Q
Common Occupational Skills711
Fuel Piping and Tubing1423
Venting, Air Supply and Draft Control1528
Controls and Electrical Systems1524
Appliances, Conversions and Fuel Storage1525
Testing and Commissioning1624
Maintenance, Repair and Decommissioning1823

Try a few

Sample Gasfitter Class B practice questions

Five sample questions from the question bank, with the answer and explanation.

Question 1
During a gas leak call, a gasfitter's combustible gas indicator reads near the lower explosive limit inside a house. What is the correct emergency make-safe action?
  • Evacuate everyone including yourself without cross-ventilating, and call for help from a safe distance
  • Open the windows and doors on opposite sides of the house to dilute the gas before leaving
  • Switch on the exhaust fans to clear the room, then return to close the main shut-off valve
  • Shut the main gas valve at the meter first, whatever the distance, then evacuate the occupants

Why: Near or above the lower explosive limit, the make-safe steps are to evacuate the building, do not cross-ventilate (it could carry an explosive mixture to an ignition source), shut the riser or cylinder valve only if it is on the way out, and phone from a safe distance. The gasfitter must not go back in to reach a valve.

Question 2
A fitter makes up a threaded steel gas pipe joint with PTFE tape. Which practice does the code require?
  • Stretch the tape, wrap it clockwise on the male threads with a 50% overlap, and leave the first two threads bare
  • Wrap the tape counter-clockwise on the female fitting with no overlap, covering every thread to the end
  • Apply tape over pipe dope on both threads so the two sealants give a double seal
  • Wrap the tape loosely in several layers over the full thread, including the starter threads

Why: A jointing sealant is applied to the male threads of a metal pipe. Tape is stretched and applied in a clockwise direction with a 50% overlap, leaving the first two starter threads bare so that loose tape cannot enter the pipe. The sealant must be certified to CAN/ULC-S642.

Question 3
A 200,000 Btuh natural gas boiler has a draft hood. The air supply is figured with 50% excess air and 10:1 air-to-gas. How much dilution air is needed?
  • 3,000 cfh
  • 2,000 cfh
  • 1,000 cfh
  • 5,000 cfh

Why: Gas flow is 200,000 / 1,000 = 200 cfh, so combustion air is 2,000 cfh and 50% excess air is 1,000 cfh. With a draft control device, dilution air usually equals the combustion air plus the excess air: 2,000 + 1,000 = 3,000 cfh.

Question 4
A natural gas meter has a 2 cu ft test dial and the dial takes 50 seconds per rotation. The gas has 1,000 Btu per cu ft. What is the appliance input? (cfh = 3,600 x dial size / seconds per rotation)
  • 144,000 Btuh
  • 72,000 Btuh
  • 100,000 Btuh
  • 36,000 Btuh

Why: Gas flow is 3,600 x 2 / 50 = 144 cfh. Input is cfh x heating value: 144 x 1,000 = 144,000 Btuh. Forgetting the dial size gives 72 cfh, or 72,000 Btuh.

Question 5
A propane service regulator is set to 10 in. w.c. All appliances are shut off. What should a manometer at an appliance inlet show about regulator lock-up?
  • The pressure rises slightly, then holds steady and stays below 14 in. w.c.
  • The pressure keeps climbing slowly, which shows the regulator is locking up
  • The pressure falls to zero within one minute, which shows positive lock-up
  • The pressure rises to 2 psig, which is normal for first-stage regulators

Why: When all appliances shut off, the pressure rises slightly before the regulator achieves positive lock-up, then stops rising. Appliance inlet pressure must stay below 14 in. w.c. or the internal gas valve will be damaged. A pressure that keeps creeping up means the regulator is not closing tightly.

FAQ

Gasfitter Class B questions, answered

How many questions are on the Gasfitter Class B Red Seal exam?

The Red Seal Gasfitter Class B exam has 100 multiple-choice questions. ExamHub's bank has 158 questions, and Test Mode draws a 100-question timed simulation.

What is the pass mark and time limit?

The Red Seal exam preparation guide states a pass mark of 70% and a writing time of four hours. ExamHub's Test Mode uses the same 70% and up to 4 hours.

What topics are on the exam?

Seven blocks: common occupational skills (7 questions), fuel piping and tubing (14), venting and air supply (15), controls and electrical systems (15), appliances, conversions and fuel storage (15), testing and commissioning (16) and service: maintenance, repair and decommissioning (18).

Do these questions come from the CSA B149.1 code book?

No. CSA B149.1 is a paid standard, so ExamHub does not reproduce it. Each question is original and cites the Red Seal standard or a public document that quotes the clause, such as a regulator bulletin, an open trade textbook or a manufacturer's instructions.

Are these the real exam questions?

No. These are original practice questions written from the Red Seal standard and free public sources. They are not copies of exam questions.

What is the difference between Gasfitter Class A and Class B?

Class B covers gas lines and gas-fired appliances up to 400,000 Btuh. Class A has no input limit and includes appliances and equipment above 400,000 Btuh, such as boilers, burners, makeup air units and process burners. Sources: the Red Seal Gasfitter overview pages and the SkilledTradesBC Gasfitter Class A program profile.

Is the Red Seal Gasfitter Class B exam open book?

You do not bring your own material. The Red Seal preparation guide says candidates are supplied with exam materials such as a math formulas sheet, an acronym list, code book information, a pencil and eraser, and a calculator if needed. SkilledTradesBC lists the B149.1 Natural Gas and Propane Installation Code as the code book provided.

Other free practice tests

TSSA G3 Gas Technician
200 questions
G3 certificate: O. Reg. 215/01 supervision, gas properties, piping and testing, venting basics and controls.
306A Plumber
128 questions
128 questions on plumbing codes, DWV, and water distribution.
427A Sprinkler Fitter
150 questions
150 questions on sprinkler and standpipe systems, fire pumps, piping and inspection, testing and maintenance.
Gasfitter Class A (Red Seal)
151 questions
Commercial and industrial gas systems, burner controls, venting, and CSA B149.
Plumber Level 1
161 questions
161 questions on safety, tools, trade math, drawings and piping.
TSSA Propane PPO-3 (ROT)
146 questions
PPO-3 cylinder filling: inspection and collar stamps, the 42% / 80% fill limits, trade measurement and O. Reg. 215/01.
TSSA OBT-3 Oil Burner Tech
150 questions
150 questions on OBT-3 scope, tanks and piping, burners, controls, venting and combustion.
CCQ Plumber (Pipe Fitter) Exam
147 questionsNew
147 questions on Quebec Plumbing Code rules: drainage, venting, water supply, tests, safety on site and maintenance.