TSSA OBT-3 Oil Burner Technician Practice Test
Free · 150 Questions.

Oil Burner Technician 3 (OBT-3): O. Reg. 215/01 scope and supervision, O. Reg. 213/01, the B139 Ontario CAD, tanks and piping, burners and nozzles, controls, venting and combustion analysis

📝 100 Q practice test✅ Pass: 75%⏱ 120 min (practice)🔁 Free retakes Updated: October 2026
⚠️ExamHub is an independent study resource and is not affiliated with, endorsed by, or reviewed by TSSA or CSA Group. Questions are original practice materials; the 100-question Test Mode is a practice length, not the official exam length.
Choose your mode
Mode 1
Test Me
100 questions with a 120-minute timer. 75% (75/100) to pass, with complete answer review at the end.
⏱ 120 min100 Qs75% to passAnswer review
Mode 2
Practice
Sequential practice with detailed explanations after every question. Numbered navigator with auto-saving progress.
📖 Explanations🔊 Voice narrationAuto-save
Or practice by topic
Acts, Regulations & the B139 Code Adoption
21 questions
Fuel Oil Properties, Safety & Tools
15 questions
Tanks, Piping & Fuel Supply
28 questions
Appliances, Burners & Technical Manuals
27 questions
Electricity Basics
15 questions
Primary Controls & Sequence of Operation
15 questions
Draft, Venting & Air Supply
15 questions
Combustion Theory & Analysis
14 questions
📲 Add TSSA OBT-3 Oil Burner Technician Practice Test to your Home Screen

Practice on the go and jump straight back to where you left off.

About the certification

TSSA Oil Burner Technician 3 (OBT-3) Certificate

In Ontario, work on oil-fired appliances and their tanks is regulated by the Technical Standards and Safety Authority (TSSA). The Oil Burner Technician 3 (OBT-3) is the entry-level certificate: under O. Reg. 215/01, s. 41, an OBT-3 holder does listed functions under general supervision on an appliance of not more than 2 U.S. gallons per hour, or any function of the supervisor’s certificate under direct supervision, and may never perform the initial activation of a new appliance.

The TSSA pass mark is 75%. TSSA does not publish the number of questions or the time allowed on the OBT-3 examination, so ExamHub’s Test Mode draws 100 questions in 120 minutes as a practice length. TSSA document FS-280-26 adopts the CSA B139 Series-24 codes with Ontario amendments.

ExamHub’s free OBT-3 practice test has 150 original questions, each with an explanation and a free public source.

CertificateOBT-3 (Oil Burner Technician 3)
RegulatorTSSA (Ontario)
Pass mark75% (official)
Official question count and timeNot published by TSSA
ExamHub Test Mode100 questions, 120 minutes (practice length)
Question bank150 original questions

Sources and last reviewed: TSSA OBT-3 curriculum (January 2025), O. Reg. 215/01 and 213/01 on e-Laws, TSSA Fuel Oil Code Adoption Document amendment FS-280-26. Last reviewed October 2026.

To see how ExamHub writes and checks questions, read About ExamHub.

What’s covered

150 practice questions, by category

Categories follow the OBT-3 curriculum theory modules: regulations, fuel oil and safety, tanks and piping, appliances and burners, electricity, controls, venting and combustion.

Topic breakdown

  • Acts, Regulations & the B139 Code Adoption21
  • Fuel Oil Properties, Safety & Tools15
  • Tanks, Piping & Fuel Supply28
  • Appliances, Burners & Technical Manuals27

 

  • Electricity Basics15
  • Primary Controls & Sequence of Operation15
  • Draft, Venting & Air Supply15
  • Combustion Theory & Analysis14

Try a few

Sample TSSA OBT-3 oil burner practice questions

Five sample questions from the question bank, with the answer and explanation.

Question 1
A holder of an OBT-3 certificate works under general supervision of an OBT-2 or OBT-1 holder on an oil-fired appliance. What is the highest input rate of appliance covered by that general-supervision list of functions?
  • Not greater than 7 U.S. gallons per hour
  • Not greater than 10 U.S. gallons per hour
  • Not greater than 2 U.S. gallons per hour
  • Not greater than 1 U.S. gallon per hour

Why: O. Reg. 215/01, s. 41(1) lists the OBT-3 general-supervision functions on an appliance with an input rate not greater than 2 U.S. gallons per hour (gph). The 7 U.S. gph figure is the OBT-2 limit (s. 40(1)); an OBT-1 has no input limit in s. 39.

Question 2
Which tank construction options does the Ontario CAD amendment give for a new steel supply tank under B139.2 (residential and small commercial)?
  • Double-bottom with interstitial monitor, non-combustible secondary containment, or 300-degree integral containment
  • Single-wall with a drip tray, a floor drain, or a high-level overfill alarm and sight gauge
  • Any fuel-oil-labelled tank under 2,500 litres, provided it is set on a level concrete pad
  • A single-wall steel tank coated with epoxy, buried in sand with a tracer wire above it

Why: Clause 6.2.1.3 as added by FS-280-26 requires steel tanks to have (a) double-bottom construction with a minimum 50 mm coverage above the bottom and a visual interstitial monitoring device, (b) non-combustible secondary containment, or (c) a minimum 300 degree integral secondary containment with monitoring of the interstitial space.

Question 3
The motor coupling on a pressure-atomizing burner is designed to break if something goes wrong. What condition is the coupling designed for?
  • If the filter plugs
  • If the oil gets cold
  • If the pump seizes
  • If the nozzle clogs

Why: The curriculum says the motor drives the pump through a pump coupling designed to break if the pump seizes, which protects the motor. The pump also provides regulated nozzle pressure and a clean cut-in and cut-out of oil flow.

Question 4
If flame is lost while the burner is firing, what does an R7184 primary control do?
  • Closes the oil valve, waits 4 minutes, then repeats ignition with no limit on attempts
  • Shuts down, waits 60 seconds in recycle, repeats ignition, and locks out after three flame losses
  • Shuts down, waits 15 seconds in recycle, repeats ignition, and locks out after five flame losses
  • Locks out immediately on flame loss and stays locked out until the reset button is pressed

Why: On flame loss the R7184 shuts down, enters a 60 second recycle delay and repeats the ignition sequence; limited recycle locks the control out after three flame losses so that repeated cycling on poor combustion is prevented.

Question 5
A technician adjusts a burner using Beckett's four-step procedure. What is the first step?
  • Set the pump pressure to zero before lighting off
  • Remove the nozzle and inspect the electrode gap
  • Adjust the air until a trace of smoke is reached
  • Increase the air until CO2 drops to 6 per cent

Why: Beckett's procedure: Step 1 adjust the air until a trace of smoke is achieved, step 2 measure CO2 (or O2) at the trace-smoke point, step 3 increase air to reduce CO2 by 1 to 2 percentage points, and step 4 recheck the smoke level, which should be zero.

FAQ

TSSA OBT-3 oil burner questions, answered

Is this the real TSSA OBT-3 exam?

No. This is unofficial study practice written from free public sources: the TSSA OBT-3 curriculum (revised January 2025), Ontario e-Laws (O. Reg. 215/01, O. Reg. 213/01, the Technical Standards and Safety Act, 2000), the TSSA Fuel Oil Code Adoption Document amendment FS-280-26, burner and control manufacturers’ instructions and Natural Resources Canada guidance. It does not reproduce the licensed CSA B139 text or real exam questions.

How many questions are on the OBT-3 exam?

TSSA does not publish the number of questions or the time allowed on the OBT-3 examination. The pass mark is 75% (TSSA Gas Technician/Oil Burner Technician Policies and Procedures, section 6).

How many questions are in the Test Mode, and what is the pass mark?

Test Mode draws 100 questions with a 75% pass mark. The 75% pass mark is official (TSSA Policies and Procedures, section 6). Because TSSA does not publish the question count or time, 100 questions in 120 minutes is ExamHub’s practice length, not the official length.

What can an OBT-3 certificate holder do in Ontario?

Under O. Reg. 215/01, s. 41, an OBT-3 holder working under general supervision of an OBT-2 or OBT-1 holder, with essential skills demonstrated and signed off, may on an appliance of not more than 2 U.S. gallons per hour do a comprehensive inspection, clean, remove and adjust a flue pipe or draft regulator, clean, lubricate and maintain an appliance, do annual-maintenance tests and adjustments, install, activate or bleed oil piping under 2 1/2 inches, and reactivate a previously installed appliance. An OBT-3 may never perform the initial activation of a new or newly converted appliance.

Which code applies to oil-burning equipment in Ontario?

TSSA’s Fuel Oil Code Adoption Document amendment FS-280-26 (dated 2 April 2026) adopts the CSA B139 Series-24 installation codes with Ontario amendments, alongside O. Reg. 213/01 (Fuel Oil). ExamHub cites only free public text, including what the TSSA document reproduces, and never reproduces paywalled CSA content.

Where do the questions come from?

They are original practice questions written by ExamHub, each with an explanation and a named public source, and mapped to the OBT-3 curriculum modules. They are not copies of exam questions.

Other free practice tests

Oil Heat System Tech (Red Seal)
167 questions
167 questions on fuel storage and supply, burners, hydronic and forced-air systems, venting, electrical controls and service.
TSSA G3 Gas Technician
200 questions
G3 certificate: O. Reg. 215/01 supervision, gas properties, piping and testing, venting basics and controls.
313A Refrigeration & A/C
150 questions
150 questions on refrigeration theory, charging, and commissioning.
TSSA G2 Gas Technician
148 questions
148 questions on G2 appliances, water heaters, furnaces, hydronic heating, venting and controls.
Plumber Level 1
161 questions
161 questions on safety, tools, trade math, drawings and piping.
CCQ Plumber (Pipe Fitter) Exam
147 questions
147 questions on Quebec Plumbing Code rules: drainage, venting, water supply, tests, safety on site and maintenance.
Gasfitter Class A (Red Seal)
151 questions
Commercial and industrial gas systems, burner controls, venting, and CSA B149.
TSSA Propane PPO-3 (ROT)
146 questions
PPO-3 cylinder filling: inspection and collar stamps, the 42% / 80% fill limits, trade measurement and O. Reg. 215/01.